Cylinder type sensing head size | M18 |
---|---|
Type | Unshielded |
Sensing method | Inductive type |
Sensing distance | 16 mm -10% to +10% |
Setting distance | 0 to 12.8 mm |
Differential distance | 10% Max. of sensing distance |
Sensing object | Ferrous metal (Sensitivity lowers with non-ferrous metals.) |
Standard sensing object | Iron 48*48*1mm |
Response frequency | DC: 0.4 kHz (average) |
Power supply voltage | 12 to 24 VDC ripple(p-p) :10% Max. |
Operating voltage range | 10 to 32 VDC |
Current consumption | 10 mA Max. |
Control output (Output type) | NPN open collector output |
Control outpu (Switching capacity) | 0 to 200 mA |
Indicator | Operation indicator(yellow) |
Operation mode | NC |
Protective circuit | Surge suppressor Output short-cut protection Output reverse polarity protection Power supply reverse polarity protection |
Ambient temperature | Operating: -40 to 70 ℃ Storage: -40 to 85 ℃ (with no icing or condensation) |
Ambient humidity | Operating: 35 to 95% RH Storage: 35 to 95% RH (with no condensation) |
Temperature influence | +/- 10% Max. of sensing distance in temperature range of -25 to +70 CEL +/- 15% Max. of sensing distance in temperature range of -40 to +70 CEL (As the basis for sensing distance of 23CEL) |
Voltage influence | +/- 1% Max. of sensing distance in rated voltage range +/- 15%. (As the basis for sensing distance at standard power voltage) |
Insulation resistance | 50 M OHM Min. at 500VDC between charged parts and the case |
Dielectric strength | 1000 VAC 50/60 Hz for 1 minute between charged parts and the case |
Vibration resistance | 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions |
Shock resistance | 1000m/s2 for 10 times each in X, Y, and Z directions |
Degree of protection | IEC60529: IP67 |
Applicable standard (EC Directive (Low Voltage Directive) ) | EN60947-1 EN60947-5-2 |
Applicable standard (EC Directive (EMC)) | EMI: EN60947-5-2 Emission Enclosure: CISPR11 Group 1 class A EMS: EN60947-5-2 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Burst: IEC61000-4-4 CE marking: Equipped |
Applicable standard (CCC mark) | Not equipped |
Connection method | Pre-wired models (Cable length: 2 m) |
Weight (Packed state) | approx. 160 g |
Material (case) | Brass nickel plating |
Material (sensing surface) | PBT |
Material (clamping nuts) | Brass nickel plating |
Material (toothed washer) | Iron zinc plating |
Electrnic components, Sensor
E2A-M18KN16-WP-C2 Cylindrical Proximity Sensor
DC 3-Wire Model ,
Unshielded , M18 , Pre-Wired Type ,
Sensing Distance 16 mm ,
Operation Mode NC ,
NPN Open Collector Output
$21.20
Based on 0 reviews
Be the first to review “E2A-M18KN16-WP-C2 Cylindrical Proximity Sensor”
You must be logged in to post a review.
There are no reviews yet.